Session Track
November 01 (Wednesday)
냉동 및 저온공학
Oral,
제5발표장(203호),
15:50~16:50
- 이영림(공주대)
We05C-4
15:50~16:50
내부열교환기를 적용한 폐열원 이용 스팀생산히트펌프의 성능에 관한 실험적 연구
This paper represents the effects of liquid/suction line heat exchanger in Steam Generation Heat Pump(SGHP) cycle. Because high DSH is necessary at basic SGHP cycle due to high compression ratio and characteristic of R245fa, basic SGHP cycle go through decrease of evaporator pressure, which result in performance degradation. This problems can be covered by applying internal heat exchanger at SGHP cycle, increasing the evaporator pressure and quality of refrigerant at evaporator inlet. By experiements with main variables of refrigerant charge, waste heat source temperature and DSH, heating capacity and COP are calculated and compared to basic SGHP cycle.
Keywords : Steam generation heat pump(스팀생산히트펌프), Waste heat source(폐열원), Internal heat exchanger(내부열교환기), Suction/Liquid line heat exchanger
Paper : We05C-4.pdf
(사)대한기계학회, 서울시 강남구 테헤란로 7길 22 한국과학기술회관 신관 702호, Tel: (02)501-3646~3648, E-mail: ksme@ksme.or.kr