We05C-4
15:50~16:50
내부열교환기를 적용한 폐열원 이용 스팀생산히트펌프의 성능에 관한 실험적 연구

이재호(서울대학교냉동시스템및콘트롤연구실), 류진우, 강대훈, 나선익, 김민수(서울대학교)
This paper represents the effects of liquid/suction line heat exchanger in Steam Generation Heat Pump(SGHP) cycle. Because high DSH is necessary at basic SGHP cycle due to high compression ratio and characteristic of R245fa, basic SGHP cycle go through decrease of evaporator pressure, which result in performance degradation. This problems can be covered by applying internal heat exchanger at SGHP cycle, increasing the evaporator pressure and quality of refrigerant at evaporator inlet. By experiements with main variables of refrigerant charge, waste heat source temperature and DSH, heating capacity and COP are calculated and compared to basic SGHP cycle.
Keywords : Steam generation heat pump(스팀생산히트펌프), Waste heat source(폐열원), Internal heat exchanger(내부열교환기), Suction/Liquid line heat exchanger